Power controller (CC-link compatible)

The CC-SSR4 is a SSR power controller compatible to CC-Link for field networks, where system configurations are increasing centered on programmable logic controllers (PLC) which play a main role in various applications in industrial equipment and production facilities.
An SSR can be used as a power controller by the serial signal from a PLC, and performs phase control and cycle control by simply changing the data.
Up to 4 SSRs can be connected to 1 controller, which is useful in reducing the wiring of a system.

Feature

  • 1 controller can control up to 4 SSRs
  • Realizes optimal control (phase control and cycle control) by an SSR through serial data from a PLC using CC-Link
  • An SSR can be selected according to the application, which realizes space-saving and low cost compare to conventional power controllers

Specifications

SpecificationsCharacteristicsRemarks
Channel typeRemote I/O channel
Number of channels1 channelSSR1-4 (Open collector output)
Power supply voltage24V±10%
SSR drive voltage30V or lessSSR1-4 (Open collector output)
SSR drive current100 mA or less (Per output)SSR1-4 (Open collector output)
Voltage drop when SSR drive terminal turns ONDC1V or less (at 100mA)
Leakage current when SSR drive terminal turns OFFDC 0.1mA or less (at 30VDC)
Power control range0~100%SSR1-4 (Open collector output)
AC voltage input rangeAC85~264Vrms* Between AC1 to AC2
AC voltage frequency range50Hz:47~53Hz/60Hz:57~63Hz* Automatic distinction for 50/60 Hz
Operating temperature range0 to 60 º C (However, no freezing)
Operating humidity range35 to 85%RH (However, no condensation)
Insulation resistance100MΩ or more(Between primary – secondary)
Withstand pressure between input/outputAC 2500Vrms(Between primary – secondary)
WeightAbout 150g
RoHS compliantO
Communication Specifications
Communication speed10M/5M/2.5M/625K/156K
Communication methodBroadcasting polling method
Synchronous methodFrame synchronous method
Encoding methodNRZI
Transmission path formatBus format (EIA RS485 compatible)
Transmission formatHDLC compatible
Error control methodCRC(X16+X12+X5+1)
* For details on CC-Link, refer to the Mitsubishi Electric Corporation’s catalog and Instructions Manual.